Type kW
HP
055
5.5
7.5
075
7.5
10
110
11
15
150
15
20
185 18.5
25
220
22
30
THD
According to IEC61000-3-12, DC Reactor is designed with 4% system impedance, and AC Reactor is designed
with 3% system impedance.
Rated Amps of AC Reactor
12
18
24
32
38
45
Chapter 7 Optional Accessories C2000 Series
Max. continuous Amps
19.8
30.6
41.4
54
64.8
77.4
7-9
Inductance mh