Chapter 12 Description of Parameter Settings C2000 Series
Feedback Signal Detection Time
Settings
Pr.08-08 is valid only for ACI 4-20mA.
This parameter sets the detection time of abnormal PID derative. If detection time is set to 0.0,
detection function is disabled.
Feedback Signal Fault Treatment
Settings
This parameter is valid only for ACI 4-20mA.
AC motor drive acts when the feedback signals analog PID feedback is abnormal.
Sleep Reference
Settings
Setting value of Pr08-10 determines if sleep reference and wake-up reference is enable or disable.
When Pr08-10 = 0, it means disable. When 08-10
Wake-up Reference
Settings
When Pr08-18 = 0, the unit of Pr08-10 and that of Pr08-11 become frequency. The settings then
become 0 ~ 600.0 Hz.
When Pr08-18=1, the unit of Pr08-10 and that of Pr08-11 switch to percentage. The settings then
switch to 0~200.00%.
And the percentage is based on the input command not maximum. E.g. If the maximum is 100 Kg,
the command now is 30kg, if 08-11=40%, it is 12kg.
The same to 08-10.
Sleep Time
Settings
When the frequency command is smaller than the sleep frequency and less than the sleep time,
the frequency command is equal to the sleep frequency. However the frequency command
remains at 0.00Hz until the frequency command becomes equal to or bigger than the wake-up
frequency.
PID Deviation Level
Settings
0.0~3600.0 sec
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0.00~600.00Hz
0.00~600.00Hz
0.00~6000.0 sec
1.0~50.0%
12-08-6
Factory Setting: 0.0
Factory Setting: 0
Factory Setting: 0.00
0, it means enable.
Factory Setting: 0.00
Factory Setting: 0.0
Factory Setting: 10.0