Delta C2000 Series User Manual page 253

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Parameter Reset
Settings 0: No Function
1: Write protection for parameters
5:
Reset KWH display to 0
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Index (Slave)
8: Reserve
9: All parameters are reset to factory settings(base frequency is 50Hz)
10: All parameters are reset to factory settings (base frequency is 60Hz)
When it is set to 1, all parameters are read only except Pr.00-02~00-08 and it can be used with
password setting for password protection. It needs to set Pr.00-02 to 0 before changing other
parameter settings.
When it is set to 9 or 10: all parameters are reset to factory settings. If password is set in Pr.00-08,
input the password set in Pr.00-07 to reset to factory settings.
When it is set to 5, KWH display value can be reset to 0 even when the drive is operating. Pr. 05-26,
05-27, 05-28, 05-29, 05-30 reset to 0.
When it is set to 6: clear internal PLC program (includes the related settings of PLC internal
CANopen master)
When it is set to 7: reset the related settings of CANopen slave.
When it is set to 6 7 9 10, please re-power the motor drive after setting.
Start-up Display Selection
Settings 0: Display the frequency command (F)
1: Display the actual output frequency (H)
2: Display User define (U)
3: Output current ( A)
This parameter determines the start-up display page after power is applied to the drive. User
defined choice display according to the setting in Pr.00-04.
Content of Multi-function Display
Settings 0: Display output current (A) (Unit: Amps)
1: Display counter value (c) (Unit: CNT)
2: Display actual output frequency (H.) (Unit: Hz)
3: Display DC-BUS voltage (v) (Unit: Vdc)
4: Display output voltage (E) (Unit: Vac)
5: Display output power angle (n) (Unit: deg)
6: Display output power in kW (P) (Unit: Kw)
7: Display actual motor speed rpm (r = 00: positive speed; -00 negative
Chapter 12 Description of Parameter Settings C2000 Series
speed) (Unit: rpm)
12-00-2
Factory Setting: 0
Factory setting: 0
Factory setting: 3