Accumulative Watt-hour of Motor in High Word (KW-Hour)
Settings
Read only
Pr.05-26~05-29 records the amount of power consumed by motors. The accumulation begins
when the drive is activated and record is saved when the drive stops or turns OFF. The amount of
consumed watts will continue to accumulate when the drive activate again. To clear the
accumulation, set Pr.00-02 to 5 then the accumulation record will return to 0.
Accumulative Motor Operation Time (Min)
Settings
00~1439
Accumulative Motor Operation Time (day)
Settings
00~65535
Pr. 05-31 and Pr.05-32 are used to record the motor operation time. To clear the operation time, set
Pr.05-31 and Pr.05-32 to 00. Operation time shorter than 60 seconds will not be recorded.
Induction Motor (IM) and Permanent Magnet Motor Selection
Settings
0: Induction Motor
1: Permanent Magnet Motor (SPM)
2: Permanent Magnet Motor (IPM)
Full-load current of Permanent Magnet Motor
Settings
0.00~655.35 Amps
Set this parameter in accord to motor's nameplate. Default setting is 90% motor drive rated current.
For example: 7.5HP 5.5kW
Setting range will be 10~30A (25*10%=2.5A
Rated Power of Permanent Magnet Motor
Settings
0.00~655.35 kW
Set motor rated power in accord to motor nameplate. Default setting is motor drive rated power.
Rated speed of Permanent Magnet Motor
Settings
0~65535 rpm
Pole number of Permanent Magnet Motor
Settings
0~65535
Inertia of Permanent Magnet Motor
Settings
0.0~6553.5 kg.cm
Chapter 12 Description of Parameter Settings C2000 Series
rated current is 25A, then Pr05-34 default is 22.5A
25*120%=30A)
2
2
(0.0001kg.m
)
12-05-8
Factory Setting: 0.0
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0
Factory Setting: #.##
Factory Setting: 0.00
Factory Setting: 2000
Factory Setting: 10
Factory Setting: 0.0