Reserved
Slip Deviation Level
Settings
0~100.0%
0: No detection
Detection Time of Slip Deviation
Settings
0.0~10.0 sec
Over Slip Treatment
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
The Pr.07-29 to Pr.07-31 are to set allowable slip level/time and over slip treatment when the drive
is running.
Motor Hunting Gain
Settings
0~10000
0: Disable
The motor will have current wave motion in some specific area. It can improve this situation by
setting this parameter. (When it is high frequency or run with PG, it can be set to 0. when the
current wave motion happens in the low frequency, please increase Pr.07-32.)
Autorestart internal of Fault
Settings
0.0~6000.0 sec
When a reset/restart after fault occurs, the drive will regards Pr.07-33 as a time boundary and
beging counting the numbers of faults occur within this time period. Within the period, if numbers
of faults occurred did not exceed the setting in Pr.07-11, the counting will be cleared and starts
from 0 when next fault occurs. However, if the numbers of faults occurred within this time period
have exceed the setting in Pr.07-11, user will need to press RESET key manually for the drive to
operate again.
Chapter 12 Description of Parameter Settings C2000 Series
12-07-10
Factory Setting: 0
Factory Setting:1.0
Factory Setting:0
Factory Setting:1000
Factory Setting:60.0