AVI Selection
Settings
0: 0-10V
1: 0-20mA
2: 4-20mA
ACI Selection
Settings
0: 4-20mA
1: 0-10V
2: 0-20mA
When changing the input mode, please check if the switch of external terminal (SW3, SW4)
corresponds to the setting of Pr.03-28~03-29.
Status of PLC Output Terminal
Settings
0~65535
Monitor the status of PLC analog output terminals
P.03-30 shows the external multi-function output terminal that used by PLC.
For Example:
If the value of Pr.03-30 displays 0002h(Hex), it means AFM1and AFM2 are used by PLC.
AFM2 0-20mA Output Selection
Settings
0: 0-20mA output
1: 4-20mA output
Chapter 12 Description of Parameter Settings C2000 Series
12-03-23
Factory Setting: 0
Factory Setting: 0
Factory Setting: ##
Factory Setting: 0