Carrier Frequency
2 15kHz
Settings
This parameter determinates the PWM carrier frequency of the AC motor drive.
Models
Setting Range
Normal Duty Factory
Setting
Heavy Duty Factory
Setting
Models
Setting Range
Normal Duty Factory
Setting
Heavy Duty Factory
Setting
Carrier
Frequency
1kH z
8kH z
15kHz
From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise. Therefore, if the
surrounding noise is greater than the motor noise, lower the carrier frequency is good to reduce the
temperature rise. Although it is quiet operation in the higher carrier frequency, the entire wiring and
interference resistance should be considerate.
When the carrier frequency is higher than the factory setting, it needs to protect by decreasing the
carrier frequency. See Pr.06-55 for the related setting and details.
Reserved
PLC Command Mask
Bit 0: Control command by PLC force control
Settings
Bit 1: Frequency command by PLC force control
Bit 2: Position command by PLC force control
Bit 3: Torque command by PLC force control
This parameter determines if frequency command or control command is occupied by PLC
Chapter 12 Description of Parameter Settings C2000 Series
230V Series
1-15HP [0.75-11kW]
02~15kHz
8kHz
460V Series
1-20HP [0.75-15kW]
02~15kHz
8kHz
Electromagnetic
Acoustic
Noise or Leakage
Noise
Significant
Minimal
12-00-13
Factory setting: Table below
20-50HP [15-37kW]
02~10kHz
6kHz
2kHz
25-75HP [18.5-55kW] 100-600HP [75-450kW]
02~10kHz
6kHz
2kHz
Heat
Dissipation
Current
M inimal
Minimal
Significant
Significant
Factory Setting: Read Only
60-125HP [45-90kW]
02~09kHz
4kHz
02~09kHz
4kHz
Current
Wave