47: Closed brake output
48: Reserved
49: Homing action complete
50: Output for CANopen control
51: Output for communication card
52: Output for RS485
53~64: Reserved
65: Output for CANopen and RS485
66: SO contact A (N.O.)
67: Analog input signal level achieved
68: SO contact B (N.C.)
This parameter is used for setting the function of multi-function terminals.
Pr.02-36~Pr.02-41 requires additional extension cards to display the parameters, the choices of
optional cards are EMC-D42A and EMC-R6AA.
The optional card EMC-D42A provides 2 output terminals and can be used with Pr.02-36~02-37.
The optional card EMC-R6AA provides 6 output terminals and can be used with Pr.02-36~02-41.
Summary of function settings (Take the normally open contact for example, ON: contact is closed,
OFF: contact is open)
Settings
Functions
0
No Function
1
Operation Indication
Master Frequency
2
Attained
Desired Frequency
3
Attained 1 (Pr.02-22)
Desired Frequency
4
Attained 2 (Pr.02-24)
Zero Speed (frequency
5
command)
Zero Speed with Stop
6
(frequency command)
7
Over Torque 1
8
Over Torque 2
9
Drive Ready
10
Low voltage warn (Lv)
11
Malfunction Indication
Mechanical Brake
12
Release (Pr.02-32)
13
Overheat
Software Brake Signal
14
Indication
Chapter 12 Description of Parameter Settings C2000 Series
Active when the drive is not at STOP.
Active when the AC motor drive reaches the output frequency
setting.
Active when the desired frequency (Pr.02-22) is attained.
Active when the desired frequency (Pr.02-24) is attained.
Active when frequency command =0. (the drive should be at RUN
mode)
Active when frequency command =0 or stop.
Active when detecting over-torque. Refer to Pr.06-07 (over-torque
detection level-OT1) and Pr.06-08 (over-torque detection
time-OT1). Refer to Pr.06-06~06-08.
Active when detecting over-torque. Refer to Pr.06-10 (over-torque
detection level-OT2) and Pr.06-11 (over-torque detection
time-OT2). Refer to Pr.06-09~06-11.
Active when the drive is ON and no abnormality detected.
Active when the DC Bus voltage is too low. (refer to Pr.06-00 low
voltage level)
Active when fault occurs (except Lv stop).
When drive runs after Pr.02-32, it will be ON. This function should
be used with DC brake and it is recommended to use contact "b"
(N.C).
Active when IGBT or heat sink overheats to prevent OH turn off
the drive. (refer to Pr.06-15)
Active when the soft brake function is ON. (refer to Pr.07-00)
12-02-14