Format 5 (Digital Electronics Corporation's Memory Link Method) - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

62.4.5 Format 5 (Digital Electronics Corporation's memory link method)

Basic format of data communication
This is the same format as the protocol of the Digital Electronics Corporation's memory link method.
For details of the basic format of data communication, refer to the following manual:
This section describes items whose settings differ from the protocols of the Digital Electronics Corporation's memory
link method and dedicated commands for a microcomputer connection of GOT.
Example: Request message for the batch read in word units (R) command in format 5 (Digital Electronics
Corporation's memory link method
Details of data items in message format
POINT
POINT
POINT
Data code during communication
Communication is performed in ASCII code.
(1) Command
Specifies the contents to access from the host to GOT.
The command is converted to a 1-digit ASCII code (Hex) and transmitted.
For details of the commands that can be used, refer to the following.
(2) Address
Specifies the head No. of the device data to be read/written.
The address notated in hexadecimal is converted to a 4-digit ASCII code (Hex) and transmitted from the upper digit.
For details of the device range that can be accessed, refer to the following.
(3) Number of points
Specifies the number of device data to be read/written. (Setting range: 1 to 40
The address notated in hexadecimal is converted to a 4-digit ASCII code (Hex) and transmitted from the upper digit.
(4) Error code
This is the response message at faulty communication appended with error contents.
The address notated in hexadecimal is converted to a 2-digit ASCII code (Hex) and transmitted from the upper digit.
For details of error codes generated in format 5 (Digital Electronics Corporation's memory link method), refer to
the following:
POINT
POINT
POINT
When connecting a microcomputer, etc. that uses the protocol of the Digital Electronics Corporation's memory link
method with the GOT
When connecting a microcomputer, etc. that uses the protocol of the Digital Electronics Corporation's memory link
method with the GOT, correct the commands to be used and the device ranges to match the specifications of the GOT.
62 - 42
62. MICROCOMPUTER CONNECTION (ETHERNET)
62.4 Message Formats
The connection manual of the device manufactured by Digital Electronics Corporation
Data length
B
42
00
00
00
00
00
H
H
H
H
H
62.4.2 List of commands
62.3 Device Data Area
 Error code list
Com-
Address
ESC
mand
R
00
06
1B
52
00
H
H
H
H
H
H
Number
of points
64
00
02
H
H
H
)
H

Advertisement

Table of Contents
loading

Table of Contents