PROFINET IO 750-340
Diagnostics
Byte
offset
3.1.7.2.1.2

Fault Types of I/O Modules with Diagnostics Capability

The fault numbers 0x0000 / 0 to 0x000F / 15 contain standard messages. The
allocated meaning of fault numbers 0x001B / 27 to 0x001F / 31 are
recommended in the specification. Starting with fault number 0x0020 / 32,
the associated fault messages are reserved or can be used according to the
manufacturer specifications.
Fault number
Data type
Significance
0x0000 / 0
Reserved, not specified
0x0001 / 1
Short circuit
0x0002 / 2
Low voltage
0x0003 / 3
High voltage
0x0004 / 4
Overload
0x0005 / 5
Over temperature
0x0006 / 6
Wire Break
0x0007 / 7
Upper limit value exceeded
0x0008 / 8
Lower limit value undershot
0x0009 / 9
Fault
0x000A / 10
...
reserved
0x000F / 15
0x0010 / 16
Configuration fault
0x0011 / 17
Transmitter or load voltage missing
0x0012 / 18
Fuse fault
0x0013 / 19
free
0x0014 / 20
Ground fault
0x0015 / 21
Reference channel fault
Description
0x0020
...
Reserved
0x003F
0x0040 Wrong F Address of the PROFIsafe I/O
module (F-Slave)
0x0041 Invalid F Address of the PROFIsafe
I/O module (F-Slave)
0x0042 Wrong F Address of the I/O Controller
(F-Host)
0x0043 Invalid F Address of the I/O Controller
(F-Host)
0x0044 SIL class is not supported
0x0045 Wrong F-CRC length
0x0046 Wrong version of the F parameter set.
0x0047 Invalid CRC of the F parameter set
0x0048
...
Reserved
0x00FF
0x0100
...
Manufacturer specific
0x7FFF
0x8000
...
Reserved
0xFFFF
WAGO-I/O-SYSTEM 750
PROFINET IO