Warning
The communication cable 750-920 must not be connected or disconnected
while the coupler/controller is powered on!

3.2.3.6 Operating mode switch

The operating mode switch is located behind the cover flap beside the con-
figuration and programming interface.
Configuration
Configuration and
interface
programming interface
Fig. 3-12: Operating mode switch
The switch is a push/slide switch with 3 settings and a hold-to-run function.

Operating mode switch

From middle to top position
From top to middle position
Lower position, bootstrap
Push down
(i.e.with a screwdriver)
An operating mode is internally changed at the end of a PLC cycle.
Attention
If outputs are set when switching over the operating mode switch from RUN
to STOP, they remain set! Switching off the software side i.e. by initiators,
are ineffective, because the program is no longer processed.
Note
With "GET_STOP_VALUE" (library "System.lib") WAGO-I/O-PRO 32
provides a function which serves to recognize the last cycle prior to a pro-
gram stop giving the user the possibility to program the behavior of the con-
troller in case of a STOP. With the aid of this function the controller outputs
can be switched to a safe condition.
Modular I/O System
®
L
W
ON
ORKS
open
flap
Function
Activate program processing (RUN)
Stop program processing (STOP)
For original loading of firmware,
not necessary for user
Hardware reset
All outputs are reset; variables are set to 0 or to FALSE
or to an initial value.
The hardware reset can be performed with STOP as well
as RUN in any position of the operating mode switch!
Fieldbus coupler/controller
Review
Mode switch
• 65
g01xx08e