5.8
Expansion Module MAC00-FP2/FP4
5.8.9
MAC00-FP2 and FP4 description of connections
The following pages describe the different aspects of connecting the modules MAC00-
FP2 and FP4.
MAC00-FP2 Connectors
MAC00-FP2 rear plate layout:
The illustration below shows all the internal connectors in the module. The Profibus and
power connectors are easy-to-use screw terminals. If the I/O's are used, they require a
JVL cable type WG0402 (2m), WG0410 (10m) or WG0420 (20m). See also the appendix
for cable and connector accessories.
Interface connector
See table for connection details
Mounting hole used
to fit the connector
board to the rear plate
Input connector
See table for connection
details
Profibus input connector
(signal from last node in the chain)
"Profibus-In" and "Profibus-Out"
Please note that these two connectors are
internally hardwired (no electronics added in between).
Terminal description:
GND
Signal ground can optionally be used for the cable screen
A-
Negative profibus signal line (Green)
B+
Positive profibus signal line (Red)
5VDC
+5VDC output to be used for external termination (optional)
JVL A/S - User Manual - Integrated Servo Motors MAC050 - 4500
Overview MAC00-FP2 connectors
Fuse T10A
Output connector
See table for connection details
Power connection
to the basic motor
Mounting hole used
to fit the connector
board to the rear plate
Profibus output connector
(signal to next node in the chain)
Connect power supply to these
2 terminals (+12-48VDC)
Profibus signal definitions
MAC00-FP2
Standard
name
wire colour
B+
Red
A-
Green
TT0965GB
Name at modules
with SN<30000
xA/xP
xB/xN
279