JVL MAC050 User Manual page 109

Integrated servo motors
Hide thumbs Also See for MAC050:
Table of Contents

Advertisement

3.2
3.2.28
Power supply circuitry (only MAC1500, MAC3000 & MAC4500)
The MAC1500, MAC3000 and MAC4500 supply is split into 2 individual circuits with full
galvanic isolation between the circuits. The control circuitry requires a voltage in the
range 18 to 32VDC and the power circuity must be supplied with 3phase 400 to
480VAC. Having 2 independent supply circuits offers the feature that the supply voltage
for the power circuitry (400-480VAC) can be removed for safety reasons, while the con-
trol circuitry can continue operating and thus keep the position counter updated and
keep other vital functions such as communication active.
P+/- must be per-
manently connected
if control circuitry
must be keept active
while main power is
disconnected.
Power
Supply
18-32VDC
Optional
400-480VAC
400-480VAC
400-480VAC
The circuit above is shown with an emergency relay (box) which can be omitted if the
application does not require this safety feature. There are shown examples of Emergency
stop and relay in
The internal power dump is intended to cover 90% of all applications but if the error
message "overvoltage" is monitored, an external power dump resistor must be connect-
ed between the terminals PD and BO.
JVL A/S - User Manual - Integrated Servo Motors MAC050 - 4500
Power Supply
MAC1500, 3000 & 4500 Supply diagram
P+
+
P-
Isolation barrier
Power dump output
PD
Bus output (560-680VDC Nom.)
BO
Bus common
CM
PE
Mains
Overvolt.
Filter
Protection
(Common mode)
L1
L2
L3
PE
STOP and RELAY
See section 5.6.2 for
further information
Emergency stop considerations, page 384
Control Core
Inrush
limiter
EMERGENCY
400-480VAC
400-480VAC
400-480VAC
Earth
Only MAC1500-4500
E
Opto
Isolators
Power dump
Dump
resistor
Driver
+
-
M
L1
L2
Three phase supply
3 x 400-480VAC nominal
L3
+ Earth
PE
TT1249-01GB
105