Chapter 7 Optional Accessories
AC output reactor is serially connected between motor drive UVW output side and motor, which
is shown as below:
Power inputs
Following table is suggested value of reactor
600V, 50/60Hz, 3-phase
KW
HP
VFD015C53A-21
2
VFD022C531-21
3
VFD037C53A-21
5
VFD055C53A-21
7.5
VFD075C53A-21
10
VFD110C53A-21
15
VFD150C53A-21
20
Wiring of AC output reactor
Rated Current
(Arms)
Saturation
LD
ND
HD
3
2.5
2.1
4.3
3.6
3
6.7
5.5
4.6
9.9
8.2
6.9
12.1
10
8.3
18.7
15.5
13
24.2
20
16.8
3% Impedance
(mH)
Current
(Arms)
LD
ND
4.2
8.806 10.567 12.580 14.677
5.9
6.144 7.338 8.806
9.1
3.943 4.803 5.743
13.7
2.668 3.222 3.829
16.5
2.183 2.642 3.183
25.7
1.413 1.704 2.032
33.3
1.092 1.321 1.572
7-8
AC reactor
(output s ide)
M
5% Impedance
(mH)
HD
LD
ND
17.612
10.239
12.230
6.572
8.005
4.447
5.369
3.639
4.403
2.355
2.841
1.819
2.201
HD
20.967
14.677
9.572
6.381
5.305
3.387
2.621