Chapter 12 Description of Parameter Settings
3. Set Pr.03-00=11 or Pr.03-23=23 or Pr.03-33=45%(9mA)
4. Refer to RTD temperature and resistance comparison table
Temperature=135 , resistance=151.71 ; Input current: 9mA, Voltage: approximately:
1.37Vdc
Temperature=150 , resistance=157.33 ; Input current:9mA, Voltage: approximately: 1.42Vdc
5. Set Pr.06=56=1.37 and Pr.06-58=10Hz. When RTD temperature increases to 135
the drive will decelerate to the selected frequency. When Pr.06-58=0, the drive will not run.
6. Set Pr.06-57=1.42 and Pr.06-29=1 (warning and decelerate to stop). When RTD temperature
increases to 150
Software Detection GFF Current Level
Settings
Software Detection GFF Filter Time
Settings
When the motor drive detects the unbalanced three-phase out current is higher than the setting of
Pr06-60, GFF protection will be activated. Then the motor drive will stop outputting.
When 3-phase current output unbalance value has exceeds Pr06-60 setting, drive will trip up
GFF and stop output immediately.
Reserved
Fault Record 1 (day)
Fault Record 2 (day)
Fault Record 3 (day)
Fault Record 4 (day)
Settings
Fault Record 1 (min)
Fault Record 2 (min)
Fault Record 3 (min)
Fault Record 4 (min)
Settings
When there is any malfunctions in motor drive operation, Pr06-17~22 will record 6 malfunctions
recently, and Pr06-63~70 can record the operation time for 4 malfunctions in sequence. It can
help to check if there is any wrong with the drive according to the recorded internal time.
For example: The first error: ocA occurs in 1000 minutes after motor drive start operation. The
second error: ocd happens after another 1000 minutes. The 4
1000 minutes. Then, the 5
error ocn happens 1000 minutes after 5
or higher, the drive will decelerate to stop and outputs an 'OH3' warning.
0.0~6553.5 %
0.00~655.35 sec
0~65535 days
0~1439 min
th
error is ocd, happening 1000 minutes following 4
th
12.1-06-23
th
error.
Factory Setting: 60.0
Factory Setting: 0.10
Factory Setting: Read only
Factory Setting: Read only
error: ocA happens after another
th
error. Last, 6
or higher,
th