Delta C2000 Series User Manual page 219

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 10 Digital Keypad
LCM Display *
The content in this chapter only applies on V1.01 and above of KPC-CC01 keypad.
Description
File is locked with password
File version dismatch
AC drive copy function time-out
Other keypad error
Corrective Actions
A setting cannot be made, because some data are
locked.
1. Verify if the data are unlocked or able to be
unlocked. If the data are unlocked, try to make the
setting again.
2. Shut down the system, wait for ten minutes, and
then power on again the system.
If none of the solution above works, contact your local
authorized dealer.
A setting cannot be made because the password is
incorrect.
1. Verify if the password is correct. If the password is
correct, try to make the setting again.
2. Shut down the system, wait for ten minutes, and
then power on again the system.
If none of the solution above works, contact your local
authorized dealer.
A setting cannot be made, because the version of the
data is incorrect.
1. Verify if the version of the data matches the motor
drive. If it matches, try to make the setting again.
If none of the solution above works, contact your local
authorized dealer.
A setting cannot be made, because data copying
timeout expired.
1. Redo data copying.
2. Verify if copying data is authorized. If it is
authorized, try again to copy data.
3. Shut down the system, wait for ten minutes, and
then power on again the system.
If none of the solution above works, contact your local
authorized dealer.
10-34