Delta C2000 Series User Manual page 420

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Treatment for Encoder/ Speed Observer Stall
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
When the motor drive output frequency exceeds Pr.1
Encoder/ Speed Observer Slip Range
Settings
0~50%
0: Disable
Detection Time of Encoder/ Speed Observer Slip
Settings
0.0~10.0 sec
Treatment for Encoder/ Speed Observer Stall and Slip Error
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
Action principle of Pr10-13~Pr10-15:
When the value of (rotation speed – motor frequency) exceeds Pr.10-13 setting, detection time
exceeds Pr.10-14; it will start to accumulate time. If detection time exceeds Pr.10-14, the
encoder feedback signal error will occur. Refer to Pr.10-15 encoder stall and slip error treatment.
Pulse Input Type Setting (PG card: PG2)
Settings
0: Disable
1: Phase A leads in a forward run command and phase B leads in a reverse
run command
A
B
2: Phase B leads in a forward run command and phase A leads in a reverse
run command
A
B
Chapter 12 Description of Parameter Settings
FW D
FW D
12.1-10-4
Factory Setting: 2
Factory Setting: 50
Factory Setting: 0.5
Factory Setting: 2
Factory Setting: 0
REV
REV

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

690v

Table of Contents