Delta C2000 Series User Manual page 451

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 14 Fault Codes and Descriptions
ID*
Fault Name
Fault
24
oH3
Motor over heat
Fault
26
ot1
Over torque 1
Fault
27
ot2
Over torque 2
Fault
28
uC
Under torque
Fault
29
LMIT
Limit Error
Fault
30
cF1
EEPROM write err
Fault
31
cF2
EEPROM read err
Fault
33
cd1
Ias sensor err
Fault
34
cd2
Ibs sensor err
Fault
35
cd3
Ics sensor err
Fault Descriptions
Motor overheating
The AC motor drive
detecting internal
temperature exceeds the
setting of Pr.06-30 (PTC
level) or Pr.06-57 (PT100
level 2).
These two fault codes will
be displayed when output
current exceeds the
over-torque detection
level (Pr.06-07 or
Pr.06-10) and exceeds
over-torque detection
(Pr.06-08 or Pr.06-11)
and it is set to 2 or 4 in
Pr.06-06 or Pr.06-09.
Low current detection
Limit error
Internal EEPROM can not
be programmed.
Internal EEPROM can not
be read.
U-phase error
V-phase error
W-phase error
Corrective Actions
1.
Make sure that the motor is not obstructed.
2.
Ensure that the ambient temperature falls within
the specified temperature range.
3.
Change to a higher power motor.
1. Check whether the motor is overloaded.
2. Check whether motor rated current setting
(Pr.05-01) is suitable
3. Take the next higher power AC motor drive
model.
Check Pr.06-71, Pr.06-72, Pr.06-73.
1. Press "RESET" key to the factory setting
2. Return to the factory.
1. Press "RESET" key to the factory setting
2. Return to the factory.
Reboots the power. If fault code is still displayed on the
keypad please return to the factory
Reboots the power. If fault code is still displayed on the
keypad please return to the factory
Reboots the power. If fault code is still displayed on the
keypad please return to the factory