Pr.
Explanation
06-00
Low Voltage Level
06-01
Over-voltage Stall Prevention
Selection for Over-voltage Stall
06-02
Prevention
Over-current Stall Prevention
06-03
during Acceleration
Over-current Stall Prevention
06-04
during Operation
Accel. /Decel. Time Selection of
06-05
Stall Prevention at Constant
Speed
Over-torque Detection Selection
06-06
(OT1)
Over-torque Detection Level
06-07
(OT1)
Over-torque Detection Time
06-08
(OT1)
Over-torque Detection Selection
06-09
(OT2)
Over-torque Detection Level
06-10
(OT2)
Over-torque Detection Time
06-11
(OT2)
06-12
Current Limit
Electronic Thermal Relay
06-13
Selection (Motor 1)
Electronic Thermal Characteristic
06-14
for Motor 1
Heat Sink Over-heat (OH)
06-15
Warning
06-16
Stall Prevention Limit Level
Fault Record 1 (Present Fault
06-17
Record)
06-18
Fault Record 2
06-19
Fault Record 3
Chapter 11 Summary of Parameter Settings
Settings
575V: 420.0~520.0Vdc
690V: 450.0~660.0Vdc
575V: 0.0~1116.0Vdc
690V: 0.0~1318.0Vdc
0: Traditional over-voltage stall prevention
1: Smart over-voltage prevention
Normal duty: 0~150% (100%: drive rated current)
Heavy duty: 0~180% (100%: drive rated current)
Light duty: 0~125% (100%: drive rated current)
Normal duty: 0~150% (100%: drive rated current)
Heavy duty: 0~180% (100%: drive rated current)
Light duty: 0~125% (100%: drive rated current)
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
0: No function
1: Continue operation after Over-torque detection
during constant speed operation
2: Stop after Over-torque detection during constant
speed operation
3: Continue operation after Over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
10~250% (100%: drive's rated current)
0.0~60.0s
0: No function
1: Continue operation after Over-torque detection
during constant speed operation
2: Stop after Over-torque detection during constant
speed operation
3: Continue operation after Over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
10~250% (100%: drive's rated current)
0.0~60.0s
0~250% (100%: drive's rated current
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
30.0~600.0 sec.
575V: 0.0~110.0
690V: 0.0~110.0
0~100% (Pr.06-03, Pr.06-04)
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
11-21
50HP and below 90.0
Factory
Setting
470.0
480.0
920.0
1087.0
0
120
150
120
120
150
120
0
0
120
0.1
0
120
0.1
170
2
60.0
105.0
50
0
0
0