Chapter 12 Description of Parameter Settings
At stop with low voltage Lv (LvS warn, no record). During operation with mid-low voltage Lv (LvA,
Lvd, Lvn error, will record).
Setting 62: when dEb function is enabled, the drive will execute dEb and record to the Pr.06-17 to
Pr.06-22 simultaneously.
Fault Output Option 1
Fault Output Option 2
Fault Output Option 3
Fault Output Option 4
Settings
These parameters can be used with multi-function output (set to 35-38) for the specific
requirement. When the fault occurs, the corresponding terminals will be activated (It needs to
convert binary value to decimal value to fill in Pr.06-23 to Pr.06-26).
0: No fault
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during constant speed(ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Stop mid-low voltage (LvS )
15: Phase loss protection (OrP)
16: IGBT over-heat (oH1)
17: Capacitance over-heat (oH2)
18: tH1o (TH1 open)
19: tH2o (TH2 open)
20: Reserved
21: Drive over-load (oL)
22: Electronics thermal relay 1 (EoL1)
23: Electronics thermal relay 2 (EoL2)
24: Motor PTC overheat (oH3) (PTC)
25: Reserved
26: Over-torque 1 (ot1)
27: Over-torque 2 (ot2)
28: Low current (uC)
29: Home limit error (LMIT)
0 to 65535 sec (refer to bit table for fault code)
Fault Code
Bit0
Bit1
current
Volt.
12.1-06-11
Factory Setting: 0
Bit2
Bit3
Bit4
OL
SYS
FBK
Bit5
Bit6
EXI
CE