Chapter 5 Main Circuit Terminals
Frame F
I n c o r r e c t i n s t a l l a t i o n m a y r e s u l t i n d a m a g e t o o p t i o n
C A U T I O N
o r i n v e r t e r . P l e a s e r e f e r t o o p e r a t i o n m a n u a l f o r
i n s t a l l a t i o n i n s t r u c t i o n s .
Ä µ §
i
¿ ù » ~ ª º ¦ w ¸ Ë ± N · | ¾ É P Å Ü À W ¾ ¹ ¤ Î ¿ ï ° t « ~ · l
¦ æ ¸ Ë ° t ¡ C
à a ¡ A ¦ w ¸ Ë « e ½ Ð ° È ¥ ² ° Ñ ¾ \ ¨ Ï ¥ Î ¤ â ¥ U « á ¤ ~ ¶ i
Main Circuit Terminals
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 +1/DC+ -/DC-
Models
VFD1600C63B-00
VFD2000C63B-00
(107 mm
VFD1600C63B-21
VFD2000C63B-21
UL installations must use 1 KVac, 75
Use copper wire only.
1. Recommended to use
2. Refer to chart 1 for the spec of terminal.
3. Refer to chart 2 for the spec of insulated tube (resistance 1 KVac).
Figure 1
5-12
Max. Wire
Min. Wire Gauge
Gauge
2/0 AWG*2
(67.43 mm2*2)
3/0 AWG*2
4/0 AWG*2
(84.95 mm
2
*2)
2/0 AWG*2
(67.43 mm
3/0 AWG*2
(84.95 mm
or 90
Ring Lug.
28.0MAX.
Torque
(±10%)
M8
2
200 kg-cm
*2)
(173 lb-in.)
2
*2)
(19.62 Nm)
2
*2)
wire.
Figure 2
Unit mm