Chapter 12 Description of Parameter Settings
Multi-function Output 1 (AFM1)
Multi-function Output 2 (AFM2)
Settings
Function Chart
0
Output frequency (Hz)
1
Frequency command (Hz)
2
Motor speed (Hz)
3
Output current (rms)
4
Output voltage
5
DC Bus Voltage
6
Power factor
7
Power
8
Output torque
9
AVI
10
ACI
11
AUI
12
q-axis current (Iq)
13
q-axis feedback value (Iq)
14
d-axis current (Id)
15
d-axis feedback value (Id)
16
q-axis voltage (Vq)
17
d-axis voltage(Vd)
18
Torque command
19
PG2 frequency command
20
Output for CANopen control
21
RS485 analog output
Analog output for
22
communication card
23
Constant voltage/current output
24
Reserved
25
CAN & 485 output
0~25
Max. frequency Pr.01-00 is regarded as 100%.
Max. frequency Pr.01-00 is regarded as 100%.
600Hz is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2 X rated voltage) is regarded as 100%
450V (900V)=100%
-1.000~1.000=100%
Rated power is regarded as 100%
Full-load torque is regarded as 100%
0~10V=0~100%
0~20mA=0~100%
-10~10V=0~100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
250V (500V) =100%
250V (500V) =100%
Rated torque is regarded as 100%
Max. frequency Pr.01-00 is regarded as 100%.
For CANopen analog output
For communication output (CMC-MOD01, CMC-EIP01,
CMC-PN01, CMC-DN01)
For communication output (CMC-MOD01, CMC-EIP01,
CMC-PN01, CMC-DN01)
Pr.03-32 and Pr.03-33 controls voltage/current output
level
0~100% of Pr.03-32 corresponds to 0~10V of AFM1.