Delta C2000 Series User Manual page 302

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

UVW Phase Magnet
45
Contractor ON/ OFF
Switch
46
Master dEb signal output
47
Brake Release at Stop
48
Reserved
49
Homing Action Complete Output when homing action complete.
Chapter 12 Description of Parameter Settings
1. Under FOCPG control mode, set MI=49 (drive enable) and
MO=45 (electromagnetic contractor ON/OFF switch), then the
magnetic contactor will follow the drive status to be ON or OFF.
2. For brake control, set MO=12 (mechanical brake release),
Pr.02-31=T1 sec (mechanical brake delay time); then
enable/disable DC braking by set 07-01 (DC brake current) to any
level except 0 and set Pr.07-02 = T2 (DC brake time at start up)
and Pr.07-03 = T2 (DC brake current at stop). It is recommend to
set T2 >T1 and try to activate brake control during zero-speed
status.
En abl e
C onta cto r
AC Driver
When dEb arises at Master, MO will send a dEb signal to Slave. Then
Slave will follow Master's command and decelerate to stop
simultaneously.
When drive stops, the corresponding multi-function terminal will
be ON if the frequency is less than Pr.02-34. After it is ON, it will
be OFF when brake delay time exceeds Pr.02-32.
Output Frequency
RUN
Multi-function
Output
MO=d47
12.1-02-16
MC
U(T1)
V(T2)
W(T3)
MOx=45
MIx=49
RUN
Motor
IM
3~
Output Frequency
< Pr.02-34
Time
02-32