If this parameter is used without DC brake, it will be invalid. Refer to the following operation
timing.
frequ ency
co mma nd
outp ut
frequ ency
RUN/STOP
Mu lti-func tion output
(mec hani cal brake
relea se)
Pr.02-11 to 0 2-14=d12
me chan ical brak e
Output Current Level Setting for Multi-function Output Terminals
Settings
0~100%
When output current is higher or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 27).
When output current is lower or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 28).
Output Boundary for Multi-function Output Terminals
Settings
0.00~599.00Hz
When output frequency is higher or equal to Pr.02-34, it will activate the multi-function terminal
(Pr.02-13, 02-14, 02-16, 02-17 is set to 29).
When output frequency is lower
(Pr.02-13, 02-14, 02-16, 02-17 is set to 30).
External Operation Control Selection after Reset and Activate
Settings
0: Disable
1: Drive runs if the run command still exists after reset or re-boots.
Setting 1:
Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will
run.
Status 2: After clearing fault once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
Chapter 12 Description of Parameter Settings
brake
or equal to
12.1-02-22
relea se
Pr.02-34, it will activate the multi-function terminal
brak e
Factory Setting: 0