Chapter 11 Summary of Parameter Settings
Pr.
Explanation
03-19
ACI Signal Loss
03-20
Multi-function Output 1 (AFM1)
03-23
Multi-function Output 2 (AFM2)
03-21
Gain of Analog Output 1 (AFM1)
Analog Output 1 when in REV
03-22
Direction (AFM1)
03-24
Gain of Analog Output 2 (AFM2)
Analog Output 2 when in REV
03-25
Direction (AFM2)
03-26
Reserved
03-27
AFM2 Output Bias
03-28
AVI Selection
03-29
ACI Selection
03-30
Status of PLC Output Terminal
03-31
AFM2 0-20mA Output Selection
03-32
AFM1 DC output setting level
Settings
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0Hz
3: Stop immediately and display ACE
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC Bus voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
11: AUI
12: Iq current
13: Iq feedback value
14: Id current
15: Id feedback value
16: Vq-axis voltage
17: Vd-axis voltage
18: Torque command
19: PG2 frequency command
20: CANopen analog output
21: RS485 analog output
22: Communication card analog output
23: Constant voltage/current output
24: Reserved
25: CAN & 485 output
0~500.0%
0: Absolute output voltage
1: Reverse output 0V; Positive output 0-10V
2: Reverse output 5-0V; Positive output 5-10V
0~500.0%
0: Absolute output voltage
1: Output 0V in REV direction; output 0-10V in FWD
direction
2: Output 5-0V in REV direction; output 5-10V in FWD
direction
-100.00~100.00%
0: 0-10V
1: 0-20mA
2: 4-20mA
0: 4-20mA
1: 0-10V
2: 0-20mA
Monitor the status of PLC output terminals
0: 0-20mA Output
1: 4-20mA Output
0.00~100.00%
11-14
Factory
Setting
0
0
0
100.0
0
100.0
0
0.00
0
0
Read
only
0
0.00