Chapter 17 Safety Torque Off Function
17-5-2-1 STO Pr06-44=0 Pr02-35=0
As shown in Figure 4: When both of STO1~SCM1 and STO2~SCM2 channel has turn off
during operating, the STO function enabling and the drive will stop output regardless of Run
command is ON or OFF status.
RUN co mmand
STO1~ SCM1
st atus
STO2~ SCM2
st atus
Drive out put
17-5-2-2 STO Pr06-44=0 Pr02-35=1
As shown in Figure 5: As same as the figure 4. But, because the Pr02-35=1, therefore, after
the Reset command, if the operating command still exists, then the drive will immediately
execute the run command again.
RUN co mmand
STO1~ SCM1
st atus
STO2~ SCM2
st atus
Drive o utput
17-5-3 STO Pr06-44=1
RUN co mmand
STO1~ SCM1
st atus
STO2~ SCM2
st atus
Drive out put