DO NOT expose the AC motor drive in the bad environment, such as dust, direct sunlight, corrosive/inflammable gasses, humidity, liquid and
vibration environment. The salt in the air must be less than 0.01 mg/cm
Installation location
Surrounding
Temperature
Rated Humidity
Air Pressure
Environment
Pollution Level
Altitude
Storage
Package Drop
Transportation
1.0 mm, peak to peak value range from 2 Hz to 13.2 Hz; 0.7 G~1.0 G range from 13.2 Hz to 55 Hz; 1.0G range from 55 Hz to
Vibration
512 Hz. Comply with IEC 60068-2-6
Impact
IEC/EN 60068-2-27
Installed vertically.
Installed
Max. allowed offset angle 10
Position
position)
IEC 60364-1/IEC 60664-1 Pollution degree 2, Indoor use only
Storage
-25 oC ~ +70 oC
Transportation
-25 oC ~ +70 oC
Non-condensation, non-frozen
Operation
Max. 90%
Storage/
Max. 95%
Transportation
No condense water
Operation/ Storage 86 to 106 kPa
Transportation
70 to 106 kPa
IEC60721-3-3
Operation
Class 3C2; Class 3S2
Storage
Class 1C2; Class 1S2
Transportation
Class 2C2; Class 2S2
If the AC motor drive is to be used under harsh environment with high level of contamination (e.g. dew,
water, dust), make sure it is installed in an environment qualified for IP54 such as in a cabinet.
If AC motor drive is installed at altitude 0~1000 m, follow normal operation restriction. If
it is install at altitude 1000~2000 m, decrease 1% of rated current or lower 0.5
Operation
temeperature for every 100m increase in altitude. Maximum altitude for Corner
Grounded is 2000m. If use at 2000 meters above sea level, please consult Delta
Electronics, Inc.