Chapter 12 Description of Parameter Settings
2-wire/3-wire Operation Control
Settings
It is used to set the operation control method:
2-wire mode 1
FWD/STOP
REV/STOP
2-wire mode 2
RUN/STOP
REV/FWD
3-wire operation control
Multi-function Input Command 1 (MI1)
(MI1= STOP command when in 3-wire operation control)
Multi-function Input Command 2 (MI2)
Multi-function Input Command 3 (MI3)
Multi-function Input Command 4 (MI4)
Multi-function Input Command 5 (MI5)
Multi-function Input Command 6 (MI6)
Multi-function Input Command 7 (MI7)
Multi-function Input Command 8 (MI8)
Input terminal of I/O extension card (MI10)
Input terminal of I/O extension card (MI11)
0: 2 wire mode 1
1: 2 wire mode 2
2: 3 wire mode
0
1
2
This parameter can be set during operation.
FWD/ STOP
REV/STOP
RUN /STOP
FWD/ REV
RUN
STOP
REV/FWD
12.1-02-1
Factory Setting: 0
FWD: ("OPEN":STOP)
("CL OSE":FWD)
REV:("OPEN": ST OP)
("C LOSE": REV)
DCM
FWD: ("OPEN ": STOP)
("CLOSE":RUN )
REV:("OPEN": F WD)
("C LOSE": REV)
DCM
F WD "CLOSE": RUN
MI1 "OPEN":STOP
REV/F WD "OPEN": F WD
"CLOSE": REV
DC M
Factory Setting: 1
Factory Setting: 2
Factory Setting: 3
Factory Setting: 4