Chapter 12 Description of Parameter Settings
No-load Current of Induction Motor 1 (A)
Settings
The factory setting is 40% motor rated current.
For model with 110kW and above, default setting is 20% motor rated current.
Stator Resistance(Rs) of Induction Motor 1
Rotor Resistance(Rr) of Induction Motor 1
Settings
Magnetizing Inductance(Lm) of Induction Motor 1
Stator inductance(Lx) of Induction Motor 1
Settings
~
Reserved
Full-load Current of Induction Motor 2 A
Settings
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. The factory setting is 90% X rated current.
Example: The rated current for 7.5HP (5.5kW) is 25A and factory setting is 22.5A. The range for
setting will be 10~30A.(25*40%=10A and 25*120%=30A)
Rated Power of Induction Motor 2 (kW)
Settings
It is used to set rated power of the motor 2. The factory setting is the power of the drive.
Rated Speed of Induction Motor 2 (rpm)
Settings
It is used to set the rated speed of the motor according to the motor nameplate.
Pole Number of Induction Motor 2
Settings
0 to the factory setting in Pr.05-01
0~65.535
0~6553.5mH
10~120%
0~655.35 kW
0~65535
2~64
12.1-05-3
Unit: Amper
Factory Setting: #.##
Factory Setting: #.###
Factory Setting: #.#
Unit: Amper
Factory Setting:#.##
Factory Setting: #.##
Factory Setting: 1710
Factory Setting: 4