Chapter 8 Optional Cards
1.
Switch off the power supply of VFD-C2000.(690V)
2.
Open the front cover of VFD-C2000 (690V).
3.
Place the insulation spacer into the positioning pin at Slot 1 (shown in Figure 3), and aim the
two holes on the PCB at the positioning pin. Press the pin to clip the holes with the PCB (shown
in Figure 4).
4.
Screw up at torque 6 ~ 8 kg-cm (5.21 ~ 6.94 in-lbs) after the PCB is clipped with the holes
(shown in Figure 5).
When VFD-C2000 (690V) is link to EtherNet, please set up the communication parameters
base on the table below. EtherNet master will be able to read/write the frequency word and control
word of VFD-C2000 (690V) after communication parameters setup.
Parameter
P00-20
P00-21
P09-30
P09-75
P09-76
P09-77
P09-78
P09-79
P09-80
P09-81
P09-82
P09-83
P09-84
P09-85
P09-86
P09-87
Slot 3
Slot 2
Slot 1
[Figure 3]
[Figure 5]
Function
Source of frequency
command setting
Source of operation
command setting
Decoding method for
communication
IP setting
IP address -1
IP address -2
IP address -3
IP address -4
Netmask -1
Netmask -2
Netmask -3
Netmask -4
Default gateway -1
Default gateway -2
Default gateway -3
Default gateway -4
Set value (Dec)
The frequency command is controlled by
8
communication card.
The operation command is controlled by
5
communication card.
0
Decoding method for Delta AC motor drive
0
Static IP(0) / Dynamic distribution IP(1)
192
IP address 192.168.1.5
168
IP address 192.168.1.5
1
IP address 192.168.1.5
5
IP address 192.168.1.5
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
0
Netmask 255.255.255.0
192
Default gateway 192.168.1.1
168
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
8-24