Delta C2000 Series User Manual page 394

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Parallel connection
Input Selection of the
PID Target Value
00-20:KPC-CC01/RS485
03-00~02:4 PID target value
Display of the PID feedback
00-04=10 display of the
PID feedback
Input Selection
of the PID Feedback
08-00:AVI/ACI
Feedback Signal Detection Time
Settings
0.0~3600.0 sec
Pr.08-08 is valid only for ACI 4-20mA.
This parameter sets the detection time of abnormal PID derative. If detection time is set to 0.0,
detection function is disabled.
Feedback Signal Fault Treatment
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
This parameter is valid only for ACI 4-20mA.
AC motor drive acts when the feedback signals analog PID feedback is abnormal.
Sleep Reference
Settings
0.00~599.00Hz
Setting value of Pr08-10 determines if sleep reference and wake-up reference is enable or
disable. When Pr08-10 = 0, it means disable. When 08-10
Wake-up Reference
Settings
0.00~599.00Hz
When Pr08-18 = 0, the unit of Pr08-10 and that of Pr08-11 become frequency. The settings then
become 0 ~ 600.0 Hz.
Chapter 12 Description of Parameter Settings C2000 Series
PID Cancelled
1
2
P
Proportion gain
08-01
D
Differential
Time
08-03
I
08-02
Integral Time
AUI/PG
12.1-08-6
08-00=0
or 02-01~06=21(disable)
PID
compensation
selection
08-16
08-21
08-04
upper limit
for
08-09
Integral
Treatment of the Feedback Signal Fault
If Hz>08-05, time exceeds 08-08
Factory Setting: 0.0
Factory Setting: 0
Factory Setting: 0.00
0, it means enable.
Factory Setting: 0.00
Frequency
command
PID Delay Time
08-07
08-05
PID F req.
output
command limit