Chapter 12 Description of Parameter Settings
Zero-speed Level of Motor
Settings
This parameter should be used with the multi-function output terminals (set to 43). It needs to be
used with PG cared and motor with encoder feedback.
This parameter is used to set the level of motor zero-speed. When the actual speed is lower
than this setting, the corresponding multi-function output terminal 43 will be ON as shown as
follows.
Max. Frequency of Resolution Switch
Settings
Switch the delay time of Max. output frequency
Settings
It is used to improve the unstable speed or unstable position due to the insufficient of analog
resolution. It needs to be used with external terminal (set to 43). After setting this parameter, it
needs to adjust the analog output resolution of controller simultaneously by this setting.
0~65535 rpm
0.00~599.00Hz
0~65000 ms
12.1-02-23
Factory Setting: 0
Factory Setting: 60.00
Factory Setting: 0