Chapter 15 CANopen Overview
1. Let Ac Motor Drive be at torque control mode: set Index 6060 = 4.
2. Set target torque: set 2060-07, unit is %, a number of 1 decimal place. For example 100 is 10.0%.
3. Operation control: Set 2060-01 = 0080H for Server on, then the motor drive will start to run to
reach target torque.
Note01 To know what the current torque is, read 2061-07 (unit is 0.1%).
Note02 To know if the torque can reach the setting value, read the bit 0 of 2061-01 (0: Not reached, 1:
Reached).
Note 03: When doing torque output and if the motor drive's speed reaches the speed limit, the output
torque will decrease to ensure the speed is under the limit.
1. Set the parameter of a trapezium curve to define position control (Pr11-43 Max. Position Control
Frequency), Pr11-44 Accel. Time of Position Control, Pr11-45 Decel. Time of Position Control)
2. Let Ac motor drive be at the position control mode, set Index 6060 = 1.
3. Set 2060-01 = 0080h, then motor drive will have server on.
4. Set target position: set 2060-05 = target position.
5. Set 2060-01 =0081h to trigger the motor drive to run to the target position.
15-16