Accumulative Watt Per Second of Motor in Low Word (W-sec)
Settings
Read only
Accumulative Watt Per Second of Motor in High Word (W-sec)
Settings
Read only
Accumulative Watt-hour of Motor (W-Hour)
Settings
Read only
Accumulative Watt-hour of Motor in Low Word (KW-Hour)
Settings
Read only
Accumulative Watt-hour of Motor in High Word (KW-Hour)
Settings
Read only
Pr.05-26~05-29 records the amount of power consumed by motors. The accumulation begins
when the drive is activated and record is saved when the drive stops or turns OFF. The amount
of consumed watts will continue to accumulate when the drive activate again. To clear the
accumulation, set Pr.00-02 to 5 then the accumulation record will return to 0.
Accumulative Motor Operation Time (Min)
Settings
00~1439
Accumulative Motor Operation Time (day)
Settings
00~65535
Pr. 05-31 and Pr.05-32 are used to record the motor operation time. To clear the operation time,
set Pr.05-31 and Pr.05-32 to 00. Operation time shorter than 60 seconds will not be recorded.
Induction Motor (IM) and Permanent Magnet Motor Selection
Settings
0: Induction Motor
1: Permanent Magnet Motor (SPM)
2: Permanent Magnet Motor (IPM)
Full-load current of Permanent Magnet Motor
Settings
0.00~655.35 Amps
Set this parameter in accord to motor's nameplate. Default setting is 90% motor drive rated
current.
For example: 7.5HP 5.5kW
Setting range will be 10~30A (25*10%=2.5A
Chapter 12 Description of Parameter Settings
rated current is 25A, then Pr05-34 default is 22.5A
25*120%=30A)
12.1-05-6
Factory Setting: 0.0
Factory Setting: 0.0
Factory Setting: 0.0
Factory Setting: 0.0
Factory Setting: 0.0
Factory Setting: 0
Factory Setting: 0
Factory Setting: