Chapter 16 PLC Functions Applications
Special D
The second area is for basic CANopen settings: (the PLC must have
to make settings)
We must set the information exchange time for the master and slave station,
Use D1090 to perform settings; setting time relationships include:
For instance, when communications speed is 500K, TXPDO + RXPDO have 8 sets, and synchronizing
time will require more than 4 ms
We must also define how many slave stations will be open. D1091 is the channel for defining station
opening, and D2000+100*n is the station number defining this channel. See the detailed explanation
below.
Slave station number n=0-7
D2000+100*n Slave station number
C2000 Series
Error code of master error
0: No error
D1074
1: Slave station setting error
2: Synchronizing cycle setting error (too small)
D1075
Reserved
D1076
SDO error message (main index value)
D1077
SDO error message (secondary index value)
D1078
SDO error message (error code L)
D1079
SDO error message (error code H)
Special D
D1090
Synchronizing cycle setting
Special D
Sets slave station On or Off (bit 0-bit 7 correspond to
D1091
slave stations number 0-7)
Description of Function
Description of Function
Description of Function
16-124
R/W
R
-
R
R
R
R
stopped
when this area is used
Default:
R/W
4
RW
R/W
RW
RW