Over-current Stall Prevention during Operation
Settings
Normal duty: 0~150% (100%: drive's rated current)
Heavy duty: 0~180% (100%: drive's rated current)
Light duty: 0~120% (100%: drive's rated current)
This parameter only works in VF, VFPG, and SVC control mode.
It is a protection for drive to auto decrease output frequency when the motor is over-load abruptly
during motor constant operation.
If the output current exceeds the setting specified in Pr.06-04 when the drive is operating, the
drive will decrease its output frequency (according to Pr.06-05) to prevent the motor stall. If the
output current is lower than the setting specified in Pr.06-04, the drive will accelerate (according
to Pr.06-05) again to catch up with the set frequency command value.
Accel./Decel. Time Selection of Stall Prevention at Constant Speed
Settings
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
It is used to set the accel./decel. time selection when stall prevention occurs at constant speed.
Over-torque Detection Selection (OT1)
Settings
0: No function
1: Continue operation after Over-torque detection during constant speed
operation
2: Stop after Over-torque detection during constant speed operation
3: Continue operation after Over-torque detection during RUN
4: Stop after Over-torque detection during RUN
Chapter 12 Description of Parameter Settings
12.1-06-4
Factory Setting: 120
Factory Setting: 150
Factory Setting: 120
Factory Setting: 0
Factory Setting: 0