Chapter 6 Control Terminals
C
Wire Gauge:
26~16 AWG (0.1281-1.318 mm
Torque:
5 kg-cm [4.3 Ib-in.] (0.49 Nm) (As shown in figure above)
8 kg-cm [6.94 Ib-in.] (0.78 Nm) (As shown in figure above)
2 kg-cm [1.73 lb-in.] (0.19 Nm) (As shown in figure above)
Wiring precautions:
Install signal wires properly and trimly in the terminals and tightened the terminals by flathead
screwdriver. Reserve at least 5 mm bare part for the signal wires to prevent the poor connection or wire
loss.
Flathead screwdriver: blade width 3.5 mm, tip thickness 0.6 mm
In the figure above, the factory setting for STO1, STO2, +24V and SCM1, SCM2, DCM is short circuit.
The factory setting for +24V-COM is short circuit and SINK mode (NPN); please refer to Chapter 4
Wiring for more detail.
Terminals
Terminal Function
+24V
Digital control signal common (Source)
COM
Digital control signal common (Sink)
FWD
Forward-Stop command
REV
Reverse-Stop command
MI 1
~
Multi-function input 1~8
MI 8
Digital frequency meter
DFM
2
);
+24V
5% 200 mA
Common for multi-function input terminals
FWD-DCM:
ON
forward running
OFF
deceleration to stop
REV-DCM:
ON
reverse running
OFF
deceleration to stop
Refer to parameters 02-01~02-08 to program the
multi-function inputs MI 1~MI 8.
Source mode:
ON: the activation current is 3.3 mA
OFF: cut-off voltage
Sink Mode:
ON: the activation current is 3.3 mA
OFF: cut-off voltage
Regard the pulse voltage as the output monitor signal
DFM
Max. current: 30 mA
Max. voltage: 30 Vdc
Duty-cycle: 50%
DCM
6-6
30~14 AWG
Factory Setting (NPN mode)
5 Vdc
19 Vdc
1% (In 30 Vdc/30 mA/RL=100 pf)
A
B
11 Vdc