Delta C2000 Series User Manual page 74

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 6 Control Terminals
When the photo-coupler is using internal power supply, the switch connection for Sink
and Source as below:
MI-DCM: Sink mode
MI-+24V: Source mode
When the photo-coupler is using external power supply, please remove the short circuit
cable between the +24V and COM terminals. The connection mode is Sink mode or
Source mode is according to the below:
The "+" of 24V connecting to "COM: Sink mode
The "-" of 24V connecting to COM: Source mode
Make sure to connect the digital outputs to the right polarity.
When connecting a relay to the digital outputs connect a surge absorber across the coil
and check the polarity.