Delta C2000 Series User Manual page 400

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

9: 8, O, 1 for ASCII
10: 8, E, 2 for ASCII
11: 8, O, 2 for ASCII
12: 8, N, 1 for RTU
13: 8, N, 2 for RTU
14: 8, E, 1 for RTU
15: 8, O, 1 for RTU
16: 8, E, 2 for RTU
17: 8, O, 2 for RTU
Control by PC or PLC (Computer Link)
A VFD-C2000 can be set up to communicate on Modbus networks using one of the following
modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote Terminal
Unit).Users can select the desired mode along with the RS-485 serial port communication
protocol in Pr.09-00.
MODBUS ASCII American Standard Code for Information Interchange : Each byte data is the
combination of two ASCII characters. For example, a 1-byte data: 64 Hex, shown as '64' in
ASCII, consists of '6' (36Hex) and '4' (34Hex).
Communication protocol is in hexadecimal, ASCII: "0", "9", "A", "F", every 16 hexadecimal
represent ASCII code. For example:
Character
ASCII code
Character
ASCII code
Data Format
10-bit character frame (For ASCII):
7, N , 2
Start
0
bit
7 , E , 1
Start
0
bit
Chapter 12 Description of Parameter Settings
'0'
'1'
'2'
30H
31H
32H
'8'
'9'
'A'
38H
39H
41H
1
2
3
7-data bits
10-bits character frame
1
2
3
7-data bits
10-bits character frame
12.1-09-2
'3'
'4'
33H
34H
'B'
'C'
42H
43H
Stop
4
5
6
bit
Even
4
5
6
parity
'5'
'6'
'7'
35H
36H
37H
'D'
'E'
'F'
44H
45H
46H
Stop
bit
Stop
bit