Motor Hunting Gain
Settings
0~10000
0: Disable
The motor will have current wave motion in some specific area. It can improve this situation by
setting this parameter. (When it is high frequency or run with PG, it can be set to 0. when the
current wave motion happens in the low frequency, please increase Pr.07-32.)
Autorestart internal of Fault
Settings
0.0~6000.0 sec
When a reset/restart after fault occurs, the drive will regards Pr.07-33 as a time boundary and
beging counting the numbers of faults occur within this time period. Within the period, if
numbers of faults occurred did not exceed the setting in Pr.07-11, the counting will be cleared
and starts from 0 when next fault occurs. However, if the numbers of faults occurred within this
time period have exceed the setting in Pr.07-11, user will need to press RESET key manually for
the drive to operate again.
Chapter 12 Description of Parameter Settings
12.1-07-10
Factory Setting:1000
Factory Setting:60.0