External Power
Supply
Note: Refer to I/O & Rlay extension card installation/ disconnecting method for PG Card installation/ disconnecting.
Terminals
Input power: 24V±5%
Maximum input current:0.5A
Note:
1) Do not connect control terminal +24V (Digital control signal common:
SOURCE) directly to the EMC-BPS01input terminal 24V.
2) Do not connect drive control terminal GND directly to the EMC-BPS01
input termina GND.
Function: When the drive only powered by EMC-BPS01, the
24V
communication can be assured and support all communication cards and
GND
following functions:
Parameters read and write
Keypad can be displayed
Keypad buttom can be operated (except RUN)
Analog input is effective
Multi-input (FWD, RV, MI 1~MI 8) needs external power supply to operate
Following functions are not supported
Relay output (including extension card) PGcard, PLC function