Chapter 6 Control Terminals
Analog input signals are easily affected by external noise. Use shielded wiring and
keep it as short as possible (<20 m) with proper grounding. If the noise is inductive,
connecting the shield to terminal ACM can have better result.
When using analog input signal in the circuit, twisted pair is suggested to use for
dealing with weak signal
If the analog input signals are affected to malfunction by noise from the AC motor drive,
please connect a capacitor and ferrite core as indicated in the following diagram.
The "COM" terminal is the common side of the photo-coupler. Any of wiring method, the
"common point" of all photo-coupler must be the "COM".
Sink Mode
external power +24V
Wind each wires 3 times or more around the core
Sink Mode
with internal power (+24VDC)
internal circuit
with external power
MI1
MI2
MI8
+24V
COM
DCM
Source Mode
with internal power (+24VDC)
Source Mode
with external power
internal circuit
external power +24V
6-2
internal circuit
MI1
MI2
MI8
+24V
COM
DCM
internal circuit