Delta C2000 Series User Manual page 247

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 11 Summary of Parameter Settings
Pr.
Explanation
07-00
Software Brake Level
07-01
DC Brake Current Level
07-02
DC Brake Time at RUN
07-03
DC Brake Time at Stop
07-04
DC Brake frequency at Stop
Voltage Incrasing Gain
07-05
Restart after Momentary Power
07-06
Loss
07-07
Maximum Power Loss Duration
07-08
Base Block Time
07-09
Current Limit for Speed Search
07-10
Treatment to Restart After Fault
Number of Times of Auto
07-11
Restart After Fault
07-12
Speed Search during Start-up
07-13
dEb Function Selection
07-14
Reserved
07-15
Dwell Time at Accel.
07-16
Dwell Frequency at Accel.
07-17
Dwell Time at Decel.
07-18
Dwell Frequency at Decel.
07-19
Fan Cooling Control
Emergency Stop (EF) & Force to
07-20
Stop Selection
Settings
575V 850.0~1116.0Vdc
690V 939.0~1318.0Vdc
0~100%
0.0~60.0 sec.
0.0~60.0 sec.
0.00~599.00Hz
1~200%
0: Stop operation
1: Speed search for last frequency command
2: Speed search for minimum output frequency
0.0~20.0 sec.
0.1~5.0 sec.
20~200%
0: Stop operation
1: Speed search starts with current speed
2: Speed search starts with minimum output frequency
0~10
0: Disable
1: Speed search for maximum output frequency
2: Speed search for start-up motor frequency
3: Speed search for minimum output frequency
0: Disable
1: dEb with auto accel./decal., the output frequency will
not return after power reply.
2: dEb with auto accel./decal., the output frequency will
return after power reply.
0.00 ~ 600.00sec
0.00 ~ 599.00Hz
0.00 ~ 600.00sec
0.00 ~ 599.00Hz
0: Fan always ON
1: 1 minute after the AC motor drive stops, fan will be
OFF
2: When the AC motor drive runs, the fan is ON. When
the AC motor drive stops, the fan is OFF
3: Fan turns ON when preliminary IGBT temperature
o
(around 60
C) is attained.
4: Fan always OFF
0: Coast stop
1: By deceleration Time 1
2: By deceleration Time 2
3: By deceleration Time 3
4: By deceleration Time 4
5: System Deceleration
6: Automatic Deceleration
11-26
Factory
Setting
895.0
1057.0
0
0.0
0.0
0.00
100
0
2.0
0.5
100
0
0
0
0
0.00
0.00
0.00
0.00
0
0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

690v

Table of Contents