Delta C2000 Series User Manual page 412

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Reserved
PLC command force to 0
Setting
0~65535
It defines the action that before PLC scans time sequence, the frequence command or speed
command needs to be cleared as 0 or not.
Bit
Bit0
Bit1
Bit2
Before PLC scan, set up the speed limit of torque control mode=0
PLC Address
Settings
1~254
CANopen Slave Address
Settings
0: Disable
1~127
CANopen Speed
Settings
0: 1M bps
1: 500K bps
2: 250K bps
3: 125K bps
4: 100K bps (Delta only)
5: 50K bps
Reserved
CANopen Warning Record
Settings
bit 0: CANopen Guarding Time out
bit 1: CANopen Heartbeat Time out
bit 2: CANopen SYNC Time out
bit 3: CANopen SDO Time out
bit 4: CANopen SDO buffer overflow
bit 5: Can Bus Off
bit 6: Error protocol of CANOPEN
bit 7: Reserved
bit 8: The setting values of CANopen indexs are fail
bit 9: The setting value of CANopen address is fail
bit10: The checksum value of CANopen indexs is fail
Chapter 12 Description of Parameter Settings
Explanation
Before PLC scan, set up PLC target frequency=0
Before PLC scan, set up the PLC target torque=0
12.1-09-14
Factory Setting 0
Factory Setting: 2
Factory Setting: 0
Factory Setting: 0
Factory Setting: Read only

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

690v

Table of Contents