Chapter 12 Description of Parameter Settings
Over-torque Detection Selection (OT2)
Settings
When Pr.06-06 and Pr.06-09 are set to 1 or 3, it will display a warning message and won't have
an abnormal record.
When Pr.06-06 and Pr.06-09 are set to 2 or 4, it will display a warning message and will have an
abnormal record.
Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT2)
Settings
Over-torque Detection Time (OT2)
Settings
When the output current exceeds the over-torque detection level (Pr06-07 or Pr06-10) and also
exceeds Pr06-08 or Pr06-11, the over torque detection will follow the setting of Pr06-06 and
Pr06-09.
When Pr06-06 or Pr06-09 is set to 1 or 3, the motor drive will have the ot1/ot2 warning after Over
Torque Detection, while the motor drive will keep running. The warning will be off only until the
output current is smaller than the 5% of the over-torque detection level (Pr06-07 and Pr06-10).
0: No function
1: Continue operation after Over-torque detection during constant speed
operation
2: Stop after Over-torque detection during constant speed operation
3: Continue operation after Over-torque detection during RUN
4: Stop after Over-torque detection during RUN
10 to 250% (100%: drive's rated current)
0.0~60.0 sec
10 to 250% (100%: drive's rated current)
0.0~60.0 sec
Ov er-t orque
det ect ion level
06- 07( 0 6- 10 )
0 6- 07( 0 6- 10) * 9 5%
Multi-fu nct ion output
terminal=7 or 8
Out put current
ON
Ov er-t orque
detec tion time
06-08(06-11
12.1-06-5
Factory Setting: 0
Factory Setting: 120
Factory Setting: 0.1
Factory Setting: 120
Factory Setting: 0.1
O N