152 Fieldbus Communication
Pos : 94.1 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Fel dbus kommuni kati on/MOD BUS/M odbus-F unktionen - Allgemeines @ 3\mod_1234513607390_21.doc x @ 27530 @ 23 @ 1
11.2

Modbus Functions

11.2.1

General

Modbus is a manufacturer-independent, open fieldbus standard for diverse
applications in manufacturing and process automation.
The Modbus protocol is implemented according to the current Internet Draft of
the IETF (Internet Engineering Task Force) and performs the following functions:
Transmission of the process image
Transmission of the fieldbus variables
Transmission of different settings and information on the coupler/controller
The data transmission in the fieldside takes place via TCP and via UDP.
The Modbus TCP protocol is a variation of the Modbus protocol, which was
optimized for communication via TCP/IP connections.
This protocol was designed for data exchange in the field level (i.e. for the ex-
change of I/O data in the process image).
All data packets are sent via a TCP connection with the port number 502.
Pos : 94.2 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Fel dbus kommuni kati on/MOD BUS/M odbus-F unktionen - Allgemeines - D atenpaket @ 3\mod_1234517576546_21.doc x @ 27536 @ @ 1
Modbus TCP segment
The general Modbus TCP header is as follows:

Table 67: Modbus TCP Header

Byte
0
Identifier
(entered by
receiver)
Additional Information
The structure of a datagram is specific for the individual function. Refer to the
descriptions of the Modbus Function codes.
Pos : 94.3 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Fel dbus kommuni kati on/MOD BUS/M ODBU S-Funktionen - Allgemeines - 15 Verbi ndungen ( x41) @ 4\mod_1235565560015_21.doc x @ 27682 @ @ 1
For the MODBUS protocol 15 connections are made available over TCP. Thus it
allows digital and analog output data to be directly read out at a fieldbus node
and special functions to be executed by way of simple MODBUS function codes
from 15 stations simultaneously.
Pos : 94.4 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Fel dbus kommuni kati on/MOD BUS/M ODBU S-Funktionen - Allgemeines - M ODBU S-Pr otokoll @ 4\mod_1235565612609_21.doc x @ 27685 @ @ 1
For this purpose a set of MODBUS functions from the Open MODBUS/TCP
specification is realized.
Manual
Version 1.3.0
1
2
3
Protocol-identifier
(is always 0)
(High byte, low
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
4
5
6
Length field
Unit identifier
(Slave
byte)
address)
7
8 ... n
Modbus
Data
function
code