Initiating Reset Functions

</dg_
You can initiate various reset functions using the mode selector switch and the
Reset button (RST).
8.7.1

Warm Start Reset

All e!RUNTIME applications are reset with a warm start reset. All global data is
set to its initialization values. This corresponds to the CODESYS V3 IDE "Reset
warm" command.
</dg_
To perform a warm start reset, set the mode selector switch to "Reset" and hold it
there for two to seven seconds.
Execution of the reset is signaled by the red "RUN LED" briefly going out when
the mode selector switch is released.
8.7.2

Cold Start Reset

</dg_
All e!RUNTIME applications are reset with a cold start reset. All global data and
the retain variables are set to their initialization values.
This corresponds to the CODESYS V3 IDE "Reset Cold" command.
</dg_
To perform a cold start reset, set the mode selector switch to "Reset" and hold it
there for more than seven seconds.
Execution of the reset is signaled after seven seconds by the "RUN" LED going
out for an extended period. You can then release the mode selector switch.
8.7.3

Software Reset

</dg_
The controller is restarted on a software reset.
To perform a software reset, set the mode selector switch to RUN or STOP and
then press the Reset button (RST) for one to eight seconds.
Reset completion is indicated by a brief orange flashing of all LEDs. After a few
seconds the SYS LED will indicate successful boot-up of the controller.
Version 1.1.0, valid from FW Version 03.08.07(20)