Avaya S8700 Maintenance Manual page 2581

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

VC-LEV (Voice Conditioner DSP Port Level)
Error Log Entries and Test to Clear Values
Table 8-712. VC-LEV Error Log Entries
Error
Aux
Type
Data
Associated Test
1 (a)
Any
None
Notes:
a. The number of VC resources in the system that are in service has fallen
below the calculated minimum value. If the number of in-service VC ports
falls below the MMCH port capacity (value entered in the Minimum
Maintenance Threshold VCs field on the system parameters maintenance
form), a VEC-LEV error is logged. If this outage continues for 15 minutes a
MAJOR alarm is raised. To resolve this alarm, correct the out-of-service
problem by following the procedures below:
1. See
2. If a VC-LEV error/alarm exist and none has been raised against
System Technician-Demanded Tests:
Descriptions and Error Code
There are no System Technician-Demanded test for VC-LEV.
555-233-143
Alarm
Level
MAJOR
''VC-DSPPT'' on page 8-1849
resolve any associated alarms.
VC-BD or VC-DSPPT MOs, a VC circuit pack may have been
removed from service causing the VC-LEV error/alarm. To resolve a
VC-LEV MAJOR alarm, restore the number of VC ports available for
service to be equal to or more than the calculated port capacity.
See
''Resolving VC-LEV Errors/Alarms'' on page 8-1858
On/Off
Board
Test to Clear Value
OFF
and
''VC-BD'' on page 8-1845
Issue 1 May 2002
to
for details.
8-1859