Siemens SINUMERIK 828D Commissioning Manual page 134

Hide thumbs Also See for SINUMERIK 828D:
Table of Contents

Advertisement

Commissioning the drive
5.1 Commissioning the drive
The following functions can also be activated:
– If you activate the "LED to flash for recognition" option, then the selected infeed will flash
– Select the filter type which is connected in front of the infeed from the list under "Line
– This option is selected if a Voltage Sensing Module has been detected.
– If you activate the external braking module option, the monitoring for the braking module
– If you set the option "Activate external braking module", the function module for the
120
alternately red-green.
filter". If it is a filter with temperature monitoring (AIM = Active Interface Module), then
this is automatically activated with the selection (default setting). This option must be
activated if you have inserted a Basic Line Filter in front of the AIM on account of loss
of the interference emission and radio interference suppression.
is activated. This requires the appropriate terminal wiring (parameter p3866 to terminal
X21.4 for S120 Booksize,) to have been established, otherwise Alarm 206900 is output.
braking module is activated. This can be used to monitor the module.
To do so, set the corresponding terminal wiring (e.g. parameter p3866 to terminal X21.4
for S120 Booksize), otherwise alarm 206900 is output. In addition, make a BICO
connection from the infeed to the free terminals on the NCU. The parameters that must
be connected for this purpose can be found in the function diagram for the braking
module in the SINAMICS S120 List Manual.
Commissioning Manual, 10/2015, 6FC5397-3DP40-5BA3