Executing the OPC UA configuration dialog
Start the OPC UA configuration dialog via the operating area "Startup > Network".
Figure 2-2
Press the "Change" button.
Table 2-1
Setting
IP address
Port
Admin User
Password
Activate OPC UA
SINUMERIK Integrate for Engineering Access MyMachine / OPC UA
Commissioning Manual, 10/2015, 6FC5397-3DP40-5BA3
OPC UA configuration dialog (initial state)
Settings of the OPC UA configuration dialog
Description
The IPv4 address of the target system. This is determined automatically.
Check these:
for the NCU and PPU
for the PCU 50
TCP port, communicates via the OPC UA. This is added to the firewall
exceptions for NCU and PPU.
(The standard for the OPC UA communication is the TCP port 4840)
Name of the administrator; with it you can add or delete other users and
assign or delete user authorizations.
Password of the administrator.
Place the checkmark to activate OPC UA and remove the checkmark to
deactivate it.
Setting up OPC UA components
-X130
Local Area Connection 2
2.2 Setup
9